Key Specifications
Parameter Value
Model PM50-C
Product Type Power Module for Modular UPS Systems
Compatible Systems Liebert APM series, Vertiv modular UPS platforms
Power Rating 50 kW / 50 kVA (unity power factor)
Topology Online double-conversion module
Input/Output
Input Voltage 380/400/415 VAC (3-phase)
Output Voltage 380/400/415 VAC (3-phase, tracking input)
Efficiency Up to 96% in online mode
Module Specifications
Form Factor Hot-swappable power module
Dimensions (W x D x H) 440 x 620 x 132 mm (17.3 x 24.4 x 5.2 in) - typical 3U height
Net Weight Approx. 25 kg (55 lbs)
Cooling Integrated variable speed fans
Performance
Power Density High power density design
Parallel Capability Multiple modules in parallel for capacity and redundancy
Redundancy Supports N+1, N+X configurations
Features
Hot-swappable Tool-less hot-swap replacement
Intelligent Control Module includes dedicated DSP controller
Display Module status LEDs
Communication Communicates with system controller via CAN bus
Battery Management Integrated battery management features
Protection Overload, over-temperature, short circuit protection
Environmental
Operating Temperature 0°C to +40°C (32°F to 104°F)
Storage Temperature -25°C to +55°C (-13°F to 131°F)
Operating Humidity 0% to 95% (non-condensing)
Altitude Up to 1000m without derating
Certifications
Compliance CE, UL, RoHS compliant
Standards IEC 62040-3, IEC 62040-2