IC65H DC 2P C32A

The Schneider Electric C65H‑DC 2‑Pole C32A Miniature Circuit Breaker is a compact DC protective device intended for use in low‑voltage direct current (DC) electrical circuits. It provides reliable overload and short‑circuit protection by combining a thermal‑magnetic trip unit with a C‑curve characteristic, making it suitable for circuits with moderate inrush currents.

open
TEL:+86 13600179521
Mail:info@hongkongeasy.com
info@hongkongeasy.com
WhatsApp
Parameters
Request a Quote
Return to List
Specifications Specification Value / Description Product Name / Model Schneider Electric C65H‑DC 2P C32A Device Type Miniature Circuit Breaker (MCB) — DC version Number of Poles 2 poles (2P) Rated Current (In) 32 A Trip Curve / Characteristic C‑curve (thermal‑magnetic) — tolerates moderate DC inrush currents Rated Operational Voltage (Ue) 250 V DC Trip Unit Type Thermal‑magnetic (overload + instantaneous) Breaking Capacity (Icu) 10 kA @ 250 V DC, per IEC 60947‑2 Rated Service Breaking Capacity (Ics) 7.5 kA (75% of Icu) Magnetic Trip Limit Approx. 8.5 × In ± 20% Rated Impulse Withstand Voltage (Uimp) 5 kV Mounting DIN‑rail (35 mm) Mechanical Life ~20 000 operations Electrical Life ~10 000 operations Standards Compliance IEC/EN 60947‑2 (DC rated MCB)